Understanding IEC 60076-3 Insulation Levels in Power Transformers

By | 05/12/2025

When engineers design a power transformer, one of the most important decisions they make is how strong the insulation needs to be. Proper insulation ensures that the transformer can survive real-world electrical stresses such as lightning, switching operations, and temporary overvoltages.

IEC 60076-3 is the international standard that governs how these insulation levels are defined and how they must be tested. In this article, we break down the ideas in this standard into clear, understandable language so anyone—engineers, technicians, or students—can follow along.

What Do “Insulation Levels” Actually Mean?

In a transformer, insulation is what separates high-voltage parts from low-voltage parts, from other windings, and from the metal tank. Without insulation, a transformer would immediately short-circuit.

IEC 60076-3 defines an insulation level as a set of withstand voltages (test voltages) that a transformer must pass to prove it is safe for operation. These withstand voltages are tested using different waveforms to simulate real electrical stress.

In other words:

The insulation level is a “performance badge” showing how much electrical stress the transformer can survive.

Each insulation level includes multiple components:

  • Lightning impulse withstand voltage (LI)
  • Chopped wave lightning impulse withstand voltage (LIC)
  • Switching impulse withstand voltage (SI)
  • AC withstand voltage (AV or LTAC)

Not every transformer needs all of these, but medium- and high-voltage units do.

Why Are IEC 60076-3 Insulation Levels So Important?

Transformers experience many types of electrical stress during their lifetime:

  • Lightning strikes entering through overhead lines
  • Switching operations in substations
  • Temporary overvoltages during faults
  • Phase-to-earth imbalances
  • Internal resonance or ferroresonance

If the insulation cannot handle these stresses, the transformer will fail—sometimes catastrophically.

IEC 60076-3 ensures the insulation is strong enough to handle these stresses before the transformer is shipped, reducing the risk of failure in the field.

The Role of “Highest Voltage for Equipment (Um)”

IEC 60076-3 makes one thing very clear:

The insulation level depends primarily on the highest voltage for equipment, called Um.

What is Um?

It is the maximum phase-to-phase voltage that the system can experience under normal conditions.
Examples:

  • A 33 kV system usually has Um = 36 kV
  • A 132 kV system usually has Um = 145 kV
  • A 220 kV system usually has Um = 245 kV

Why does Um matter?

Because the higher the system voltage, the higher the possible overvoltage stresses—and therefore the stronger and thicker the insulation must be.

IEC 60076-3 uses Um to determine:

  • Required lightning impulse test voltage
  • Required AC withstand voltage
  • Required switching impulse test voltage
  • Required chopped wave test voltage

All of these values are standardized in Table 2 of the standard.

Uniform vs Non-Uniform Insulation

IEC 60076-3 distinguishes between uniform and non-uniform insulation.

✔ Uniform insulation

All ends of a winding have the same insulation level.

Most distribution transformers and many medium-voltage transformers fall in this category.

Example:

  • A 33 kV winding has LI = 170 kV at both ends.

✔ Non-uniform insulation

One terminal—usually the neutral—has a lower insulation level than the line terminals.

This is common in:

  • High-voltage transformers
  • Star-connected windings
  • Windings with grounded neutrals

Why?

Because the neutral is at or near earth potential during normal operation, so it does not need to withstand as great an overvoltage as the line ends.

IEC 60076-3 provides specific rules for assigning insulation levels to the neutral.

Components of an Insulation Level

Every insulation level consists of several test voltages. Let’s break them down in simple terms.

Lightning Impulse Withstand Voltage (LI)

This simulates real lightning strikes entering through overhead transmission lines.

IEC 60076-3 defines:

  • A standard 1.2/50 µs lightning impulse
  • A specific peak value for each Um (e.g., 550 kV for Um = 123 kV)

The transformer must withstand:

  • Five full-wave impulses at 100% test voltage
  • Two lower-level shots for calibration
  • No internal flashover or failure

This test is mandatory for:

  • All windings with Um > 72.5 kV
  • Type test for Um ≤ 72.5 kV windings

Chopped Wave Lightning Impulse (LIC)

This is a more severe lightning impulse test. The wave is chopped early by a rod gap, creating a steeper voltage rise.

LIC includes higher peak values than LI.
For many high-voltage transformers (Um > 170 kV), LIC is mandatory.

LIC tests are especially important when:

  • The transformer is connected to GIS (gas-insulated switchgear)
  • The system has rod gaps
  • Very fast transients may occur

Switching Impulse Level (SI)

Switching impulses simulate slow-front overvoltages caused by:

  • Circuit breaker reclosing
  • Fault clearing
  • Line energization
  • Ferroresonance
  • Temporary overvoltages

SI tests use:

  • A much longer impulse (250–300 µs)
  • A high peak value (e.g., 750 kV for Um = 245 kV windings)

Switching impulse tests are:

  • Required for Um > 72.5 kV
  • Always routine tests for Um > 170 kV

AC Withstand Levels (AV / LTAC)

These simulate power-frequency overvoltage conditions:

  • Earth faults
  • Unbalanced loads
  • Voltage regulator issues
  • Temporary system disturbances

AC withstand tests:

  • Are performed for 60 seconds
  • Use sinusoidal AC
  • Must not collapse or flashover

IEC 60076-3 distinguishes between:

  • AV = applied voltage test (between winding and earth)
  • LTAC = line terminal AC test (only line terminal stressed)

These tests are routine for all transformers.

Induced Overvoltage Tests (IVW and IVPD)

These verify insulation between:

  • Turns
  • Discs
  • Layers
  • Phases

✔ IVW (Induced Voltage Withstand)

The winding is energized at twice (or more) the rated frequency to avoid saturation.
The test lasts 60 seconds.

✔ IVPD (Induced Voltage with Partial Discharge Measurement)

This is a more sensitive test used to detect insulation defects.
IEC 60076-3 gives:

  • Test voltages: 1.8 × Ur (enhanced voltage)
  • PD measurement levels: 1.58 × Ur
  • Test durations (5 minutes, or 1 hour for high voltage)

For high-voltage transformers, IVPD is mandatory as a routine test.

How IEC 60076-3 Selects the Required Test Set

Table 1 of the standard shows which tests apply to each voltage class.
For example:

  • Um ≤ 72.5 kV: No switching impulse is required; LI is a type test, not routine.
  • 72.5 < Um ≤ 170 kV: LI is a routine test; SI is a special test if ordered.
  • Um > 170 kV: LIC and SI are mandatory routine tests.

In simple terms:

The higher the voltage → the more severe and comprehensive the test set.

How Insulation Levels Appear on a Rating Plate

IEC 60076-3 requires the insulation level to be written in a standardized format:
Um / SI / LI / LIC / AC

Example (from the file):

For a 66/11 kV transformer with Um = 72.5 kV on the HV side:

  • LI = 325 kV
  • AC = 140 kV

It appears on the nameplate as:

HV: Um 72.5 / LI 325 / AC 140 kV

This makes it easy for customers and maintenance teams to know what the transformer is designed to withstand.

Neutral Insulation Requirements

The standard gives dedicated rules for neutral insulation:

  • Directly earthed neutral → minimum 38 kV AC withstand if Um ≥ 17.5 kV
  • Non-directly earthed neutral → customer must specify Um and test voltage

Neutral impulse tests (LIN) are optional but recommended if the neutral can become “floating.”

External Insulation and Clearances

IEC 60076-3 also provides recommended external clearances in air.
The idea is simple:

The external clearances must be at least strong enough to withstand the internal insulation tests.

Altitude correction is required above 1000 m.

Clearances increase with altitude because air becomes less dense and less insulating.

How Insulation Levels Are Selected in Real Projects

In a typical transformer project, insulation levels are chosen using the following logic:

Step 1: Identify the system voltage

Example: 132 kV system → Um = 145 kV.

Step 2: Choose the insulation level row in Table 2

For Um = 145 kV, LI = 650 or 550 depending on purchaser’s risk level.

Step 3: Consider system conditions

  • Is the transformer near GIS?
  • Are switching surges frequent?
  • Is lightning density high?

Step 4: Assess purchaser requirements

Some utilities require higher-than-standard insulation for reliability.

Step 5: Confirm tests required (routine/type/special)

Based on Um and whether insulation is uniform or non-uniform.

Why Higher Insulation Levels Are Not Always Better

Engineers sometimes assume that “bigger is better,” but higher insulation levels come with drawbacks:

  • Larger clearances inside the windings
  • Bigger bushings
  • Heavier transformer
  • Higher material and manufacturing cost
  • More complex winding geometry

IEC 60076-3 aims to avoid unnecessary overspecification by setting standardized levels that are coordinated with typical system overvoltages.

Conclusion: The Core Purpose of Insulation Levels

Insulation levels make sure transformers:

  • Can survive lightning surges
  • Can handle switching surges
  • Are safe against temporary AC overvoltages
  • Are free from dangerous partial discharges
  • Match the system voltage they serve
  • Last for decades without insulation failure

IEC 60076-3 sets standardized, proven test methods to validate all of these aspects before a transformer ever leaves the factory.

Author: Zakaria El Intissar

I’m a power automation engineer passionate about innovation in the energy sector. I specialize in control systems and SCADA solutions for electrical substations. With strong hands-on experience, I design, implement, and optimize these critical technologies to keep energy infrastructures running reliably. I’ve also worked on renewable-energy projects, where I helped develop new solutions that support a sustainable energy transition.

Leave a Reply

Your email address will not be published. Required fields are marked *